Cmp TMC2 User Manual Page 1

Browse online or download User Manual for Accessories communication Cmp TMC2. CMP TMC2 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
INSTALLATION INSTRUCTIONS FOR
CABLE CONNECTOR TYPE TMC2
CMP TYPE TMC2 CABLE CONNECTOR FOR USE WITH INTERLOCKED & CORRUGATED CONTINUOUSLY
WELDED METAL CLAD (TYPE MC OR MC-HL) OR TECK ARMORED AND ARMORED & JACKETED CABLES
IN ORDINARY, WET & HAZARDOUS LOCATIONS.
INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC
CMP Document No. FI410 Issue 4 0113
0518
Glasshouse Street St. Peters Newcastle upon Tyne NE6 1BS
Tel: +44 191 265 7411 Fax: +44 191 265 0581
E-Mail: [email protected] Web: www.cmp-products.com
Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the
following standards:-
EN60079-0:2009, EN60079-7:2007, EN60079-21:2009, BS 6121:1989, EN50262:1998 (Amd 2001), EN61241-0:2006, EN61241-1:2004
Dr Geof Mood - Technical Director - (Authorised Person)
DUBAI HOUSTON NEWCASTLE SINGAPORE SHANGHAI PUSAN PERTH
www.cmp-products.com
Cable Connector Selection Table
Logo’s shown for illustration purposes only. Please check certification for details
CABLE CONNECTOR
CABLE CONNECTOR
TYPE TMC2
TYPE TMC2
Order Reference Entry Thread
Min
Thread
Length
Cable Armor
Diameter
Cable Jacket
Diameter
Across
Flats
Across
Corners
Nominal
Assembly
Length
Approx Weight
Aluminium
(Ozs)
Aluminum NP Brass S. Steel NPT Option Min Max Min Max
TMC2-050A075 TMC2-050NB075 TMC2-050SS075 1/2” - 0.78
0.42 0.63 0.50 0.75 1.20 1.30 1.65 2.29
TMC2-075A075 TMC2-075NB075 TMC2-075SS075 - 3/4” 0.80
TMC2-050A099 TMC2-050NB099 TMC2-050SS099 1/2” - 0.78
0.60 0.89 0.69 0.99 1.48 1.60 1.97 3.00
TMC2-075A099 TMC2-075NB099 TMC2-075SS099 - 3/4” 0.80
TMC2-075A118 TMC2-075NB118 TMC2-075SS118 3/4” - 0.79
0.79 1.10 0.87 1.18 1.81 1.95 2.13 5.11
TMC2-100A118 TMC2-100NB118 TMC2-100SS118 - 1” 0.98
TMC2-100A137 TMC2-100NB137 TMC2-100SS137 1” - 0.98
0.94 1.28 1.02 1.37 2.05 2.21 2.34 6.70
TMC2-125A137 TMC2-125NB137 TMC2-125SS137 - 1-1/4” 1.00
TMC2-125A162 TMC2-125NB162 TMC2-125SS162 1-1/4” - 1.00
1.22 1.50 1.30 1.62 2.36 2.55 2.44 8.82
TMC2-150A162 TMC2-150NB162 TMC2-150SS162 - 1-1/2” 1.06
TMC2-125A190 TMC2-125NB190 TMC2-125SS190 1-1/4” - 1.03
1.49 1.72 1.57 1.90 2.56 2.79 2.44 9.45
TMC2-150A190 TMC2-150NB190 TMC2-150SS190 - 1-1/2” 1.06
TMC2-150A200 TMC2-150NB200 TMC2-150SS200 1-1/2” - 1.06
1.57 1.88 1.65 2.00 2.75 2.97 2.60 11.06
TMC2-200A200 TMC2-200NB200 TMC2-200SS200 - 2” 1.57
TMC2-150A233 TMC2-150NB233 TMC2-150SS233 1-1/2” - 1.06
1.79 2.21 1.91 2.33 2.95 3.19 2.64 12.77
TMC2-200A233 TMC2-200NB233 TMC2-200SS233 - 2” 1.57
TMC2-200A272 TMC2-200NB272 TMC2-200SS272 2” - 1.57
2.14 2.61 2.27 2.72 3.54 3.82 2.76 24.69
TMC2-250A272 TMC2-250NB272 TMC2-250SS272 - 2-1/2” 1.57
TMC2-300A325 TMC2-300NB325 TMC2-300SS325 3” - 1.63
2.49 2.97 2.62 3.25 4.33 4.68 3.46 42.68
TMC2-350A325 TMC2-350NB325 TMC2-350SS325 - 3-1/2” 1.68
TMC2-350A376 TMC2-350NB376 TMC2-350SS376 3-1/2” - 1.68
2.95 3.54 3.16 3.76 4.84 5.23 3.68 53.44
TMC2-400A376 TMC2-400NB376 TMC2-400SS376 - 4” 1.73
TMC2-400A425 TMC2-400NB425 TMC2-400SS425 4” - 1.73 3.52 3.94 3.70 4.25 5.23 5.65 3.89 59.19
All dimensions in inches
TECHNICAL DATA
CABLE CONNECTOR TYPE : TMC2
INGRESS PROTECTION : IP66, NEMA 4X
PROCESS CONTROL SYSTEM : BS EN ISO 9001
: ISO/IEC 80079-34:2011
HAZARDOUS AREA CLASSIFICATION
ATEX CERTIFICATION No : SIRA 09ATEX1164X
ATEX CERTIFICATION CODE : II 2 GD Ex e IIC Gb / Ex ta IIIC Da
IEC Ex CERTIFICATION No : IEC Ex SIR.09.0068X
IEC Ex CERTIFICATION CODE : Ex e IIC Gb / Ex ta IIIC Da
CSA-Us CERTIFICATION No : 09.2194053X
CSA-Us CERTIFICATION CODE : Class I, Div 2 Groups A, B, C, D; Class II, Div 2, Groups E,F,G; Class III, Div 2; Encloxure type 4X;
Ex e II, Class I Zone 1, AEx e II, AEx ta IIC
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
INSTALLATION GUIDANCE NOTES
1. In accordance with NEC requirements, connectors with NPT and Metric entry threads are suitable for both Divisions and Zones.
2. In accordance with CEC requirements, connectors with NPT threads are suitable for both Divisions and Zones. Connectors with Metric threads are
only suitable for Zones unless fitted with an approved Metric to NPT thread conversion adaptor.
SPECIAL CONDITIONS FOR SAFE USE
1. Entry component threads may need additional sealing to maintain the ingress protection rating as applicable to the associated equipment in which
it will be attached
2. The cable ranges shall only be used where the temperature, at the point of entry, is in the following ranges:
TMC Types: -60°C to +110°C.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer
Page view 0
1 2

Summary of Contents

Page 1 - TYPE TMC2

INSTALLATION INSTRUCTIONS FORCABLE CONNECTOR TYPE TMC2CMP TYPE TMC2 CABLE CONNECTOR FOR USE WITH INTERLOCKED & CORRUGATED CONTINUOUSLYWELDED METAL

Page 2 - CABLE CONNECTOR COMPONENTS

INSTALLATION INSTRUCTIONS FOR CMP CABLE CONNECTOR TYPE TMC2DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTHDUBAI • HOUSTON • NEWCAST

Comments to this Manuals

No comments