INSTALLATION INSTRUCTIONS FOR
A2FFC CONDUIT GLAND
CONDUIT GLAND FOR USE WITH UNARMOURED AND BRAID ARMOURED CABLES
INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC
CMP Document No. FI412 Issue 6 1012
Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the following standards:-
EN 60079-0:2006, EN 60079-1:2007, EN 60079-7:2007, EN 60079-15:2005, BS 6121:1989, EN 50262:1998 (Amd 2001), EN 61241-0:2004, EN 61241-1:2004.
Dr Geof Mood - Technical Director - (Authorised Person)
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
www.cmp-products.com
Cable Connector Selection Table
Logo’s shown for illustration purposes only. Please check certification for details
CONDUIT
CONDUIT
GLAND
GLAND
TYPE
TYPE
A2FFC
A2FFC
C
able
Connector
Size
Entry
T
hread
“C”
Min Entry
Thread
L
ength “E”
M
ax
Envelope
Diameter
“
D”
Protrusion
L
ength
“F”
Diameter Of Cable
“
A”
Typical Diameter Of
A
rmour Conduit
“
B”
Ordering
R
eference
(Brass Metric)
Cable
Connector
Weight
(
Kgs)
Metric ID OD ID OD
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 4.3 5.1 9.8 20S16A2FFC1RAC000 0.044
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 5.8 6.8 9.0 20S16A2FFC1RA001 0.048
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 6.6 7.8 11.6 20S16A2FFC1RAC004 0.05
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 8.0 9.1 13.9 20S16A2FFC1RAC009 0.05
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 8.1 9.5 13.0 20S16A2FFC1RAC010 0.05
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 8.1 10.2 14.0 20S16A2FFC1RAC020 0.054
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 8.1 10.9 15.9 20S16A2FFC1RAC025 0.054
20S16 M20 X 1.5 15.0 29.0 17.0 3.2 8.1 11.7 15.9 20S16A2FFC1RAC030 0.056
20S M20 X 1.5 15.0 29.0 17.0 6.1 9.9 10.9 15.9 20SA2FFC1RAC025 0.057
20S M20 X 1.5 15.0 29.0 17.0 6.1 11.7 13.0 16.0 20SA2FFC1RAC040 0.057
20S M20 X 1.5 15.0 29.0 17.0 6.1 11.7 13.9 18.9 20SA2FFC1RAC045 0.059
20S M20 X 1.5 15.0 29.0 17.0 6.1 11.7 14.7 18.7 20SA2FFC1RAC060 0.061
20 M20 X 1.5 15.0 34.0 21.0 6.5 14.0 13.0 16.0 20A2FFC1RAC040 0.057
20 M20 X 1.5 15.0 34.0 21.0 6.5 13.1 15.6 21.0 20A2FFC1RAC050 0.082
20 M20 X 1.5 15.0 34.0 21.0 6.5 14.0 16.9 20.5 20A2FFC1RAC066 0.086
20 M20 X 1.5 15.0 34.0 21.0 6.5 14.0 18.0 21.0 20A2FFC1RAC070 0.09
20 M20 X 1.5 15.0 34.0 21.0 6.5 14.0 18.7 24.0 20A2FFC1RAC075 0.09
20 M20 X 1.5 15.0 34.0 21.0 6.5 14.0 20.0 23.5 20A2FFC1RAC080 0.095
20 M20 X 1.5 15.0 34.0 51.0 6.5 14.0 20.5 27.0 20A2FFC1RAC085 0.095
25 M25 X 1.5 15.0 44.0 25.0 11.1 15.3 17.6 25.0 25A2FFC1RAC100 0.115
25 M25 X 1.5 15.0 44.0 25.0 11.1 18.7 20.7 26.0 25A2FFC1RAC105 0.115
25 M25 X 1.5 15.0 44.0 25.0 11.1 20.0 22.3 26.5 25A2FFC1AC110 0.115
25 M25 X 1.5 15.0 44.0 25.0 11.1 20.0 23.7 30.8 25A2FFC1RAC115 0.124
25 M25 X 1.5 15.0 44.0 25.0 11.1 20.0 25.1 29.0 25A2FFC1RAC120 0.124
25 M25 X 1.5 15.0 44.0 25.0 11.1 20.0 26.5 34.0 25A2FFC1RAC180 0.124
32 M32 X 1.5 15.0 45.5 29.0 17.0 26.0 28.1 32.0 32A2FFC1RAC250 0.182
32 M32 X 1.5 15.0 45.5 29.0 17.0 26.3 30.4 38.0 32A2FFC1RAC280 0.188
32 M32 X 1.5 15.0 45.5 29.0 17.0 26.3 35.0 43.0 32A2FFC1RAC290 0.188
40 M40 X 1.5 15.0 50.0 30.0 23.5 32.2 36.4 44.0 40A2FFC1RAC300 0.23
40 M40 X 1.5 15.0 50.0 30.0 23.5 32.2 40.0 48.0 40A2FFC1RAC380 0.23
50S M50 X 1.5 15.0 50.0 30.0 31.0 38.2 46.5 58.7 50SA2FFC1RAC450 0.3
50S M50 X 1.5 15.0 50.0 30.0 31.0 38.2 51.2 60.0 50SA2FFC1RAC500 0.3
50 M50 X 1.5 15.0 50.0 30.0 35.6 44.1 51.2 60.0 50A2FFC1RAC550 0.34
All dimensions in millimeters
TECHNICAL DATA
CABLE GLAND TYPE : A2FFC
INGRESS PROTECTION : IP66, NEMA 4X
PROCESS CONTROL SYSTEM : BS EN ISO 9001
ISO/IEC 80079-34:2011
HAZARDOUS AREA CLASSIFICATION
ATEX CERTIFICATION No : SIRA06ATEX1097X, SIRA07ATEX4326X
ATEX CERTIFICATION CODE : II 2/3 GD Ex d IIC, Ex e II, Ex nR II, Ex tD A21 IP66 - Equipment Zone 1, 2, 21 & 22,
Gas Groups IIA, IIB & IIC
IEC Ex CERTIFICATION No : IEC Ex SIR.06.0040X
IEC Ex CERTIFICATION CODE : Ex d IIC / Ex e II / Ex nR II, Ex tD A21 IP66
CSA CERTIFICATION No : 1211841
CSA CERTIFICATION CODE : Ex d IIC / Ex e II, Enclosure Type 4x
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions
before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
• The A2FFC shall only be used where the temperature, at the point of entry, is between -60°C and +130°C.
• The entry component threads may need additional sealing to maintain the ingress protection rating as applicable to the associated equipment to
which it will be attached.
• The A2FFC is only suitable for flexible conduit installations. Cables must be effectively clamped to prevent pulling or twisting.
0518